      What are some methods of estimating GPM flow on small 10-20 ton process chillers with no water pressure ports.

      All i have is a tank temp sensor and a leaving water temp sensor the pump is constant speed . Can i estimate gpm by using delta T?

      Member Post, Member Post and 2 others
      7 Comments
      • @AGON17 you can calculate the GPM, but you will need to know the tonnage you are pulling from the water it needs to be accurate if you want an accurate result.

        12,000 BTU’s = 1 ton
        The ANSI standard is 2.4 GPM/ton and 10 degree delta T with 44°F leaving water and 54°F entering water on the evap.

        1. Using tons: GPM = (24 × Tons) / ΔT
        Example: (24×100 Tons) / 10°F = 240 GPM

        2. Using Press drop across evap: GPM₂ = GPM₁ × √(ΔP₂/ΔP₁)
        For future use if you need it: GPM1 and Delta p1 are oem design, 2 is measured.

        3. You can also check pressure drop across pump, and use the pumps flow curve in the pump manual to calculate GPM.

        All of this will not be as accurate as taking a pressure reading, and comparing it to design.

        I’m sure some other guys will chime in as well. let us know

        • @the-chiller-guys that all sounds good on paper. Without knowing the pressure drop, anything is just a guess.

          Guy needs to buy a gauge. It’s not going to break the bank!!!

          1
          • @craig-moodie agreed, but he mentioned there is no pressure ports, i think he just wants a ballpark for an idea of where his problem is. If its 2 am, im going to calculate it, and go back and install pressure taps at a shutdown.

            I agree though, pressure taps should be welded on if they aren’t there. @AGON17 A good follow up should include a tap on supply and return with valves going to a common gauge.

            1
            • @craig-moodie yeah unfortunately not pressure taps so an estimate is as good as I’m gonna get. They are small 20 ton scroll 410a process chillers with constant volume pumps

              1
            • @the-chiller-guys Thanks for the detailed update!

              1

      Submit a Support Ticket

      Are you facing a technical problem with the website or the online portal?
      Submit a support ticket, and we will get back to you within 48 hours.

      ✓

      Ticket Submitted!

      Thank you! Your support ticket has been submitted. We will get back to you within 48 hours.

      The Chiller Guys Hub

      Join the Chiller Guys Community

      Create a free account to keep reading and unlock full access to our community.

      • Access the full news feed & discussions
      • Share knowledge with like minded guys
      • Get exclusive training content
      • Join thousands of chiller mechanics worldwide