Member Post posted an update
Recover hose set up
Im recovering 4160Ib of R134a I have a recovery set up that works ok but I would like to see some other set ups, I know we are doing push and pull im just looking for hose set up
Member Post, Member Post and 3 others4 Comments-
We use this recovery machine, push pull with 3/4 inch hoses. In this case im pulling 3/4″ from bottom of evap and pushing in condensor (in the photo im pushing with 1/2″). Our machine has 4 valves to switch discharge and suction so you dont have to move hoses to pull the last vapour from the machine. this took 6 hours or so to pull 1200kg to 0kpaG
2 -
For that amount of refrigerant , you better use water cooled recovery machine , Trane offers one ,
-