      need to remove a Carrier 30hx screw compressor with two compressors which one of them the o-ring on suction pipe is leaking ,

      Q1 : can we pump the system down using liquid line valve and-discharge valve

      Q2 : After repair , do I have to add oil to the system? or what ever is in condenser is enough

      Q3 : Which way is better , pump down (if possible) or recovery of refrigerant

      Member Post, Member Post and 2 others
      6 Comments
      • I would recommend pulling the gas, especially if there is a leak. Then you know how much has been lost. Prevents call backs. As for the oil, you should be good, most 30HX units have sight glasses for the oil, check level there. Should have a full lower sight glass minium. If it does not have sight glasses, there will be an oil level switch, watch it under the inputs while running.

        2
      • The screws should not be pumped down, damage to the screws will occur. There should be a tag on the pecker head of the screw saying not to drop the suction pressure below 10psi.

        2
      • if you do not want to pull the gas. isolate and use your recovery machine to pump over. do not pump down.

    Submit a Support Ticket

    Are you facing a technical problem with the website or the online portal?
    Submit a support ticket, and we will get back to you within 48 hours.

    ✓

    Ticket Submitted!

    Thank you! Your support ticket has been submitted. We will get back to you within 48 hours.

    The Chiller Guys Hub

    Join the Chiller Guys Community

    Create a free account to keep reading and unlock full access to our community.

    • Access the full news feed & discussions
    • Share knowledge with like minded guys
    • Get exclusive training content
    • Join thousands of chiller mechanics worldwide