      YCAV Oil Filter

      Does anyone have documentation on checking oil filter for a York YCAV?

      Member Post, Member Post and Member Post
      8 Comments
      • There is no real check you can do!

        Have you done an oil analysis? That will give you good information on whether it should be changed or not. If your chiller has isolation valves, then its a pretty easy job to do, and to be honest, nt expensive, so it could be a good idea to do it.

        Is there a big pressure drop between discharge and oil pressure?

      • High Differential Oil Pressure Cutout Fault

        The High Differential Oil Pressure Cutout protects the compressor from low oil flow and insufficient
        lubrica-tion, possibly from a dirty oil filter. A system will fault and shut down with a controlled
        ramped shutdown when its Discharge to Oil Differential Pressure rises above the cutout of 65 PSID.
        This safety is ignored for the first 90 seconds of run time. This safety measures the pressure
        differential between discharge and oil pressure, which is the pressure drop across the oil filter.
        The Status display fault message for this safety is shown below:
        SYSTEM SAFETIES (FAULTS)
        SYS X YYYYYYYY HIGH DIFF OIL PRESSURE

        • Low Differential Oil Pressure Cutout Fault
          The Low Differential Oil Pressure Cutout protects the
          compressor from low oil fl ow and insuffi cient lubrication.
          A system will fault and shut down with a controlled
          ramped shutdown when it’s differential between oil
          and suction pressure falls below the cutout. This safety
          assures that the compressor is pumping suffi ciently to
          push oil through the oil cooling circuit and through the
          internal compressor lubrication system. The Status
          display fault message for this safety is shown below:
          SYS X YYYYYYYY LOW DIFF OIL PRESSURE
          X indicates the system and YYYYYYY indicates the
          system is in a “FAULT” condition and will restart when
          the 120 second anti-recycle timer times out or “LOCKOUT”
          and will not restart until the operator clears the
          fault using the keypad.
          The safety is ignored for the fi rst 60 seconds of run time.
          After the fi rst 60 seconds of operation, the cutout is linearly
          ramped from 0 PSID to 30 PSID in 5 to 10 minutes
          based on ambient temperature. See TABLE 13 for the
          ramp times for the given ambient temperatures.

          • TABLE 13 – LOW DIFFERENTIAL OIL PRESSURE
            CUTOUT
            AMBIENT TEMPERATURE
            TABLE 13 – LOW DIFFERENTIAL OIL PRESSURE
            CUTOUT
            AMBIENT TEMPERATURE RAMP
            TIME
            > 50ºF 5 Minutes
            > 45ºF 6 Minutes
            > 40ºF 7 Minutes
            > 35ºF 8 Minutes
            > 30ºF 9 Minutes
            >=30ºF 10 Minutes

            A 30 second safety bypass below 50 Hertz is employed during rampdown. The bypass is primarily
            needed under conditions where another compressor is being brought on and the running compressor is
            being ramped down to 5 Hertz to add the additional compressor due to load requirements. Under these
            conditions, the slow speed of the running compressor(s) causes the oil differential to become very
            low, especially if the water temperature is high and the suction pressure is high. The bypass
            as-sures the compressor(s) will not trip on a nuisance low oil differential fault.
            High Discharge Temperature Cutout Fault

          Submit a Support Ticket

          Are you facing a technical problem with the website or the online portal?
          Submit a support ticket, and we will get back to you within 48 hours.

          ✓

          Ticket Submitted!

          Thank you! Your support ticket has been submitted. We will get back to you within 48 hours.

          The Chiller Guys Hub

          Join the Chiller Guys Community

          Create a free account to keep reading and unlock full access to our community.

          • Access the full news feed & discussions
          • Share knowledge with like minded guys
          • Get exclusive training content
          • Join thousands of chiller mechanics worldwide