• Member Post posted an update

      August 7, 2026

      YMC2 Inverter Baseplate temps

      Hi guys

      Was looking at a ymc2 going off on high inverter baseplate alarm

      Cleaned the water side of hx, quoting a coolant side flush

      I want to know what you think good operating temps are for inverter baseplate at 90-100% and at 50%

      After the cleaning I had phase

      A-163 B-165 C-173 @Member Post%

      A-122 B-123 C-126 @Member Post%

      What temp ranges do you look for at 50 & 100%

      Member Post and Member Post
      2 Comments 1 Share
      • 100 degrees or less would be good this one was doing 170 degrees or more going into alarms they can be cleaned with a small circulation pump but I have not seen it done before

        1
        • Jordan Steiner on Facebook is your best friend when it comes to anything YMC2

          1