Member Post posted an update
Has anyone had issues with a York YLAA machine and intermittent condenser fan problems? It’s a 454B machine and will run with BAS command for about 10 min and I’ll lose all fans on circuit 1. All fans are on an AYK580 drive. I can run in service mode and have no issues. It’s there a firmware update or any known issues with the I/O board that I should be looking in to? Thanks
Member Post, Member Post and Member Post3 Comments-
Did you get this solved?
-
Yes. I found chafed wires in the chase under the coils. The drive never displayed ground fault. Weirdest thing. Fixed the wiring and that solved the issue.
2-
@stephen-tatarzewskigmail-com Yeah normally you would get a ground fault, especially on the YVAA chillers.
Good work there getting it sorted.
-
-