• Member Post posted an update

      May 1, 2025

      @Member Post Smith

      “Does anyone have any information to share on why Trane has 2 Igv actuators on this F machine? Its a wye delta start machine. Curious if they independently position the vanes to optimize performance or if they are just synchonizing the vanes and just eliminated the linkages.”

      Member Post and Member Post
      4 Comments
      • It is because that is what they call an extended capacity chiller, which was originally in just 2 sizes a 1470 and 1720 and then they came out with a smaller 3rd one a 1300 ton machine. I believe it’s just because everything is beefier so they went with the two actuators.

      • When binding the sensors originally there is a place in the configuration that you specify if you have one or two actuators and that’s really it, the software will do everything else.