Hi Everyone.I had this call on a Trane CVHF870. Was tripped on oil differential.
I checked the pompe on manuel = amp was ok, pressure was swinging, sight glasses empty. So I added 2.5 gallons of OEM oil and did the test again. The pressure got stable, oil level still not visible.
Conditions: condenser water in was at 46°F
I ran the chiller for more than 3 hours with the condenser valve chocked to bring back some of the oil…not really happened.
Question: Is there anything else that could have been done?
Is it possible to have a bad seal internally and lose the oil or usually is because of the cold condenser water? Logs show 15000 running hours and 180 starts.
Thanks in advance.
Member Post, Member Post and 2 others1 Comment-
is it 514A
-