      Have a york yvaa that blew the transient suppressor board and all 3 input power fuses. However have performed the catostrophic failure test and drive tests and everything checks ok. Before calling jci would like to make sure there are no other tests i could perform to verify any problems. Also line voltage is consistent at incoming side of the disconnect. Just not convinced there is nothing that caused this.

      Member Post, Member Post and 3 others
      2 Comments
      • Member Post (edited)

        @timothy-lupa Hey brother,

        I posted this in the “screw chillers group”, so all of us get emailed. In the future, if you post in a private group, responses will be a lot faster.

        Keep an eye on my post and yours.

        • Was it a lightening strike possibly ? or some insect , are all other fuses and circuit breakers ok, if so then disconnect the output leads to the compressors and see if you get DC buss and a Low Current alarm when you try to start , you do not need the Transient Suppressor Board in circuit to run the chiller