Member Post posted an update February 20, 2026
Trane CVHE450, 2003 Model, Overhaul 2017
Looking for some advice on the following… Units needs the Motor windings temperature sensors replaced. Owner wants to do it in the field. Trane recommends to send the motor off to be redone.
Has anyone replaced these in the field? Does Trane make a kit with the parts needed to epoxy them into the stator in the field?
- View more comments
-
Member Post posted an update March 6, 2026
Wsc063
Hello
could you support me with the following diagram? I’m having problems with a mcquay wsc chiller because of the low engine current problem, at the time of checking I found that the % rla does not go up from 0% and when I want to see the electrical diagram there is no information why it is destroyed
Label 330273001
- View more comments
-
Member Post posted an update March 6, 2026
BLUEBOX
Hi guys!
I’m looking for some tech books, manuals or anything from which I could learn more about BlueBox by Swegon…Do you have any idea where could I find something useful?
Tnx in advanced!
- View more comments
-
Member Post posted an update March 6, 2026
-
Member Post posted an update May 20, 2025
@Member Post
Hi Everyone.I had this call on a Trane CVHF870. Was tripped on oil differential.
I checked the pompe on manuel = amp was ok, pressure was swinging, sight glasses empty. So I added 2.5 gallons of OEM oil and did the test again. The pressure got stable, oil level still not visible.
Conditions: condenser water in was at 46°F
I ran…
- View more comments
-
Member Post posted an update February 26, 2026
Bitzer Compressor
Would any have information on the start cycle for a Bitzer CSV screw compressor?
About 10 seconds into the run cycle, a 230 volt 10 amp fuse is opening. Just trying to see what actually happens when its starts up. Its a VSD compressor.
I have checked all the auxiliary solenoids within the heat-pump, panel fans etc but can’t seem to get to…
- View more comments