• Member Post posted an update

      May 5, 2026

      YCIV has 3 sensors on 1 circuit not reading, the voltages are fine to the board, but the display will not give me a value. The board is now obsolete and needs a retrofit. Any work around?

      Member Post, Member Post and Member Post
      5 Comments 1 Share
      • Member Post (edited)

        Do you have some more info? Nameplate, photos, which sensors.

        Do you have another machine on site?

      • Are those sensors landed on the same plug into the micro board? Likely are. Check to see if any of the pins have widened out a bit and maybe now making contact.
        You could also swap the plugs to system # 2 and see if the problem follows to that system

        1
        • @chillmac had this happen to me on an old YCIV. Molex plug connectors behind the main board (board is mounted on a plate/hinge that swings out). Oil pressure transducer wasn’t reading. Bad connection. Didn’t find the issue until AFTER I replaced a perfectly good transducer.

        • In about a month or 2 we will be replacing a YCIV if you tell me exactly what board or parts you need I can try and remove the for you

          1

      Submit a Support Ticket