YCIV has 3 sensors on 1 circuit not reading, the voltages are fine to the board, but the display will not give me a value. The board is now obsolete and needs a retrofit. Any work around?
Member Post, Member Post and Member Post5 Comments 1 Share-
Do you have some more info? Nameplate, photos, which sensors.
Do you have another machine on site?
-
@John_Clemmer oil temperature, suction temperature and discharge temperature
-
-
Are those sensors landed on the same plug into the micro board? Likely are. Check to see if any of the pins have widened out a bit and maybe now making contact.
You could also swap the plugs to system # 2 and see if the problem follows to that system1-
@chillmac had this happen to me on an old YCIV. Molex plug connectors behind the main board (board is mounted on a plate/hinge that swings out). Oil pressure transducer wasn’t reading. Bad connection. Didn’t find the issue until AFTER I replaced a perfectly good transducer.
-
-
In about a month or 2 we will be replacing a YCIV if you tell me exactly what board or parts you need I can try and remove the for you
1
-