      Ecochiller. Air cooled scroll chiller

      Is anyone familiar with Ecochillers? The factory support is almost non existent and cant get ahold of them. Hoping someone here has experience with them. To make it short, its got a carel controller and tied to bms. I get evaporator freezing alarms, it kicks the alarm if the suction sat temp is like 28 degrees for more than 2 minutes. It trips once to twice a week at random times of the day and random ambient temps. Return water is always between 55-58 degrees. I cant find anything that corresponds when it trips. Never lose flow and have constant flow, it doesnt trip when the lead lag pumps switch over. Ive verified the pressure transducer readings againt probes and they are almost dead nuts. When its running suction sat sits around 35 to 42 degrees and of course