Trane RTAC screw machine does anyone have a part number for the liquid level canister and probe? The one i see on line isnt the one i have and im not sure i can install it unless we get trane to come out it says “software needed” i know the trane sensors meed to be bind wasnt sure if that was the same thing or is this ganna be a new board i need to add
Member Post, Member Post and Member Post2 Comments-
@jcardone213yahoo-com Your best bet is using the Trane comfortsite RPL tools for finding parts, or call Trane parts.
You will need the Techview program for Binding, and possibly config (We have videos on youtube for installing the program and binding)
Do you have Techview (for the ch530), or something else?
-
@John_Clemmer I found the correct one I had to upgrade to the new version no more ball float it’s now a probe, yes I have tech view but I need to have Trane come out and do a software update apparently I can’t do the update only binding sensors and other parts but my next problem I have to figure out why all 7 condenser fans are coming on befor the compressor starts I don’t see anything on tech view about fan staging, I only have an option for standard fan or quiet fan I think it said, they whole start of this I was getting high evap approach (32degrees) found the level was reading 0.0 but I had no ref in the barrel pulled the gas and see i have contaminated ref (3 tanks all pressures are different) but I found the ball is getting stuck so it wasn’t opening the exv
On circuit 2 I had an issue also but I removed 3.5 gallons of oil from the evap barrel and that was throwing of the liquid level also
-
-