York YS Chiller moving excessive amount of oil on a recently rebuilt compressor. We stepped into this chiller after a previous contractor had done work. When the charge was pulled it was missing almost 9 gallons of oil. Total oil charge is 10g for this specific YS model. Any thoughts…
Member Post, Member Post and 3 others5 Comments-
What is the model number Full? Normally on a YS you charge by Discharge Superheat only not by book stated charge and it typically winds up being about 100 lbs or more less then the book. if you do put the book charge in the machine it can move excess oil out the oil Seperator and push in the refrigerant charge and the oil will not come back through the rotors like it should. it will pick up and drop out before entering the rotors for return. let me know model of chiller and the charge you put in as well as Refrigerant type.
-
Hello Brian,
Here’s the model, York M/N: YSBBBBSO-CFD
R-22
I didn’t charge it , but from my understanding it was taken back to nameplate ( 460# R-22 )
-
Gotcha its a style D Machine Little machine SO what discharge sh you running on this? I would take it to 400Pounds then slow walk it up to try to get Discharge SH to 40-45 and approach to 2-3 if its a two pass. Theses old R-22 screws’ we had to short charge a little to ensure we would not push oil out of separator. Is their a reasonable steady load there? I will be right back to you as I look up the changes on D rev
1 -
I’m gonna have to reach out to the apprentice who charged the chiller for the DIsch SH . The load is iffy as the building is partially unoccupied, it’s a 8 story building. Definitely could see low condenser water temps for a good part of the year.
-
Remember, oil likes to hang out in the cold spots of the chiller. ALSO when you recover refrigerant, oil can/will travel with the refrigerant. When recharging, distill the refrigerant (long and painful process) to get only the refrigerant to recharge the chiller.
Refrigerant floats on Oil.1
-