      Daikin AGZ Series

      Im working on a 50 Ton Daikin AGZ. System is grossly oversized for application. I currently have Circuit 1 Tandum out for quote but were trying to keep Circuit 2 online. It started out once in awhile C2 Low Evap Pressure but now its everyday. Compared physical pressures to transducers and both read accurately. System has a new flow switch installed about a month ago. Systems not low on charge on C2. Weve had multiple techs onsite and after cycling power chiller runs and operates then trips between 12am-2am.

      • @jturnbough99

        Do you know if they calibrated the flow switch?

        If you have the thermal dispersion switch, it’s very easy.

        The chiller is just responding to the conditions. Could be flow, a configuration issue, system issue, etc..

        Only way we can point you in the right direction is with a log sheet.

        Can you complete the following:

        1. check the pressure drop across the water side on the evap, and compare it to the flow chart for that model evap in the IOM

        2. verify all sensors and transducers are calibrated.

        3. fill out a log sheet (we have them in the “technician resources in the member files”)

        Once we know you have good data, and we can see the data, we can tell you where the issue is.

        • Member Post (edited)

          Is this at the same time every day? I would check the pumps and BMS

          • sounds like BMS is cutting pumps off and closing valves before cycling chiller

        Submit a Support Ticket

        Are you facing a technical problem with the website or the online portal?
        Submit a support ticket, and we will get back to you within 48 hours.

        ✓

        Ticket Submitted!

        Thank you! Your support ticket has been submitted. We will get back to you within 48 hours.

        The Chiller Guys Hub

        Join the Chiller Guys Community

        Create a free account to keep reading and unlock full access to our community.

        • Access the full news feed & discussions
        • Share knowledge with like minded guys
        • Get exclusive training content
        • Join thousands of chiller mechanics worldwide