• “Hey I think y’all didn’t wire some of the sensors back correctly on the chiller.”
      “We did a point-to-point check, what makes you think that?”
      *Sends following photo*

      Member Post, Member Post and 2 others
      2 Comments
      • Haha almost!

        Did they just get done changing a discharge sensor?

        1
        • @John_Clemmer They had just gotten done re-wiring a bunch of sensors including the compressor discharge ones after they got the compressor installed.

          One of our suction sensors later did the same thing, turned out they had screwed the appleton box cover on to the wire and nicked it! 😑 That was a fun repair.

          Somehow too, the labels for the capacity slide and slide stop got swapped during the install, so trying to commission and tune the chiller the compressor wasn’t working right. We decided to hit the autocalibration on the slide sensors and the compressor immediately started screaming until it tripped a few seconds later.
          If you ever want to go on an adventure with a screw, simply swap the wires for the slide valve and slide stop!