Constant High Oil Temp Alarm
Hey guys, just wanted to share and pick everyone’s mind and gather different thoughts. I am currently working on a Trane RTAC Chiller for a good client of our company. I have been working on this issue for about 6 months now because the chiller was neglected and has severely gone years without proper service. My first inspection of the unit had me extremely upset by its condition. Always tripping on an High oil temperature alarm, serverly damaged and compromised condenser coils, oil and never been checked or tested, and found that we were constantly burning condenser fans motors. I was extremely upset the chiller was left to rot over the span of nearly 10 ten years. Automatically recommended replacing the chiller but found it would be months to a year before it could even arrive here. The goal now is to prevent more condenser fans motor losses and bring down the oil temps and head pressure while we wait for the replacement Chiller.
First thing I have done was replace the oil and oil filters on both circuits. Did not want the old oil to compromise the screw compressors. Then I also made a sprinkler system to help cool down the oil and also bring our head temps down. Then set the running limit from 100% to 80%. Afterwards its been about 2 months and was sent back for the same Alarm. Found out that someone else was just replacing the fan motors without finding out why. They already replaced 6 fan motors since my last visit. I found another fan motor had gone bad. I felt really bad for this client having to waste so much money on the fans. Spent a good morning digging deep to find the problem.
There are a total of 7 fans per circuit. There is no VFD control either. The 30A fuses had also gone bad too. The circuit for the fans are 3 phase 460V with 30A fuses. We have 1 fan to 1 contactor and the rest are wired for 2 fans into one contactor. So 4 contactors per circuit. I know the fans would be running at higher amps to due the bad air flow through the coils. Each motor is rated for 2.4A. The circuits with 2 motors on one contactor have a total amperage of 4.8A. Our amperage when measured after each contactor was averaging 6.9A. When comparing to the rated amperage of our motors and calculated total, these fans are running 143% overloaded. But wait there’s more! I wanted to find the cause of our blown fuses. I know the 30A rating is mainly to allow inrush current on start up. But to have them blow had me curious. To find out i needed to replace the bad fan motor and fuses first. Cleared the alarm and let the chiller run. I climb up to watch see how the fan stage on and off and back on. Saw alot of them spins in reverse, or windmilling, when staged off and idling. I knew the motors run extremely hard and noticed when they spin in reverse, the rotation speed is about 80-90% the speed of the fans that are running. When the chiller calls for the next stage of fans to run, they aggressively fight the windmilling to rotate in the right direction and takes a while to spin up. When measuring that in rush current at start we draw dangerously close to LRA for an extended amount of time as the motor fights the windmill effect. Essentially its cooking the the insulation with how hot the windings would get. So I reported my findings, with data, back to the client and said give me a few days to find a solution.
After talking back and forth with our foremans, and other techs, and with Trane. My boss wanted me to try installing clutches on all the fans. Immediately said “no” because they would not fit the clearance within the shroud and would require fan blades with a larger hub. With 14 fans total, it’s too costly for the client to accept after spending alot on new motors. So I thought about adding baffles to section off our fans per stage. It would stop drawing through the idling fans and focuses more on drawing through the coils. We could have our sheet metal guys fab some baffles and they’d be simple to install. I dont think it would affect the overall performance of the condenser since we already had the sprinklers in place. In theory it could improve it slighty due to each section focusing air draw on the coil instead of the path of least resistance which would be the idling fans. Its a solution thats not costly and could buy us some time before the new chiller is ready. But I do have my doubts and wanted to ask you guys what you think about it. Any thoughts and opinions would help. Is there any other solutions? Also I have thought of installing soft starters and over current realys but those wouldn’t work with the inrush current that each motor takes. So baffling is the solution im left with that makes sense.
Member Post, Member Post and 4 others5 Comments-
Forgot to mention that all of the temp sensors and pressure transducers have been checked and verified they’re reading correctly. Also needed to disable DDC controls since it doesnt respond to any equipment and was locking the chiller at 100% running limit even though i used tech view to set running limit to 80%.
-
I think it would be easier to find what still works on this chiller than what doesn’t, what a read!
While I personally have not had issues with those line of chillers, a different person in my industry has where they were constantly burning out fan motors and getting windmilling on the others, their plant fab shop came up the same solution of adding baffles and it certainly helped. Much easier solution than clutches. I would suggest going this route especially if a replacement might be due in the future, which is really should as most air condensing chillers only last about 15 years, maybe 20 with good maintenance.
Some other things I would look for are if the oil cooler has any build up or is clogged, have seen that before where due to deposits and otherwise just flushing out the oil and replacing the filters doesn’t work especially with neglect. There are some controls suggestions but it sounds like that was already dealt with on your end.I hope that helps, keep us updated on the progress with this cursed chiller.
-
1. Do not run water on coils. Usually water will cause calcium build up and will end up scaling the tubes over long period of time.
I typically will use a heavy concentration of foam brite on the coil but it definitely needs to be cleaned from inside out.
If you still hate having high head pressure you should try a foaming cleaner again with a steam pressure washer.
2. The RTAA was the original design the RTAC had replaced. For some reason the first RTAC Trane decided to take the oil cooler which was in the condenser coils out.
Trane makes a Oil Cooler Retrofit for this. You will need to pull the charge and oil in order to do this but I would go this route. It has taken care of my issue that on these. Definitely won’t regret plus the compressors are on these chillers are some of the best screws ever made.
3. If you replace the oil filter did you replace the oil control valve / check valve which is right behind the oil filter on the compressor. Make sure you change that too. These will start to stick on you and usually get forgotten. FYI you will need a 2in socket if remember correctly to pull the old one out and put the new one in. -
If have txv just adjust only
-
I spent 24 years working for TRANE, air cooled and water cooled products.
From what you have described, you most likely have, the coils are heavily impacted (air flow through the coils is blocked).1. DO NOT USE FOAM BRITE on the coils. It is an ACID based product, It will kill the coils.
2. Wash the coils from the inside to the outside, Pushing the dirt back out eat way it came in.
3. The Compressor(s) have an oil return line from the bottom of the evaporator to the compressor, it should be cold and sweating. There is a filter DHY in that line, and a solenoid valve (depending on how many compressors there on that Ckt).
4. Install a Tee in the oil pressure transducer line and connect a refrigerant stubby gage to verify oil pressure from your gage to the transducer.
5. Does your machine have an Oil Cooler? If so, verify operation of the TXV for the oil cooler. The oil cooler is located near/at the compressor. The oil cooler is a BPHE (Brazed Plate Heat Exchanger) about the size off a ½ sheet piece of paper. Usually installed for low ambient operation.
6.. When replacing the Kepler valve, tighten to 165 Lb. FT. Make sure you clean out the cavity, and replace the O-RING..
7. Have you verified OIL LEVEL in the Oil Separator?
8. If the condenser coils are flaking (due to use of improper/acid based coil cleaner, inadequate rinsing of coil cleaner, and are impacted. REPLACE the COILS.
9. TRANE offers a program called R’NEWAL, which offers replacing coils, compressors, metering devices, controls upgrade from CH550 to Tracer TU… which is a fraction to the cost of like kind replacement of the chiller.
10. Just a follow-up question, what are the clearances around this machine, is it located in an area with adequate air flow, as described in the IOM?
Respectfully,
Mike2
-