-
Member Post posted an update
September 11, 2026 (edited)
RTAF
I have a Trane 410t RTAF. I have circuit 1 locked out on the HMI. As it is being repaired and is on a vaccum. I am looking to run circuit 2 but the low evap pressure on circuit 1 inhibits circuit 2 from running. I have been reading document # RTAF-SVX001P-EN and I cannot find why circuit 1 is holding off circuit 2. I have 75psia in the evap of circuit 2.
Member Post, Member Post and 3 others5 Comments-
Ran into similar situation on same chiller. I had disconnect off on circuit 2 to do a repair and it shutdown circuit 1. Never figured out why, always curious though.
Ended up electrically isolating what I was working on and put disconnect back on. Chiller started back up.
Was a while ago but I don’t remember any alarms either
1 -
If it’s on a service port i installed a service T in-between the pressure transducer and the angle valve. With angle valve front seated bumped up pressure transducer above low pressure cutout and other circuit should start.
-
In plug the suction pressure transducer for the circuit you are working on. You may get a loss com fault for it, however the other circuit will run
1 -
Cuando esto ocurra, lo mejor es desconectar el transductor de baja presión y se activará una alarma de pérdida de comunicación. Borre la alarma de baja presión y podrá reiniciar el circuito. Se apaga como medida de seguridad porque detecta una posible fuga.
-
Before recovery of Ckt-1, either isolate the Ckt-1 suction pressure transducer COV, or remove it from the connection point and let read OA pressure. Then proceed with your evacuation/repairs.
-