• Member Post posted an update

      November 23, 2026 (edited)

      Purge filter drier

      Hi Gents,

      Has anyone ever changed out the filter drier on a purge system, specifically on a cvhf-650 TRANE unit. It almost seems like this unit has three lines coming or going to the purge unit. The filter drier has a port on it which i suspect I have to do something with. Any insight you guys have or literature would be greatly appreciated. Thank you in advance. I will gladly buy you a cup of coffee. 619-571-2637

      • If you have 3 lines then you have an Earthwise purge. You still only need to close the larger line coming in and the line leaving the purge drier. Follow the 1/4″ line in your picture at the leaving side of the sight glass and close that line off. If the purge has been running there may be liquid refrigerant in the drier so you would need to connect a refrigerant hose to the Tee fitting on the drier and connect the other end down on the evaporator to drain the liquid out. You can use a little heat to make it move easier. Remove the hose when down, change the drier, pull a vacuum on the drain fitting, open all valves and you’re finished. Clean the air cooled condenser if needed.

        • This Chiller is currently off I feel that changes my setup. Also, I don’t think I have a long enough hose. I was thinking that for the 1st time I do this I should use a recovery machine recovery tank and vacuum pump along with my manifold gauges. Your method is so much and easier though.

        • Member Post (edited)

          @navaircon

          Looks like Jody already helped you out, but heres a decent guide Me and some Trane techs made awhile back if your on the PM in case you didn’t have it yet.

      Submit a Support Ticket

      Are you facing a technical problem with the website or the online portal?
      Submit a support ticket, and we will get back to you within 48 hours.

      ✓

      Ticket Submitted!

      Thank you! Your support ticket has been submitted. We will get back to you within 48 hours.

      The Chiller Guys Hub

      Join the Chiller Guys Community

      Create a free account to keep reading and unlock full access to our community.

      • Access the full news feed & discussions
      • Share knowledge with like minded guys
      • Get exclusive training content
      • Join thousands of chiller mechanics worldwide