      “I’m going to install two YLAA155 air cooled chillers for process cooling using 45% DowTherm SR1. Standard evaporator flow is 2.2gpm/Ton. Is there a need for a correction factor with glycol?

      Has anyone used heat recovery option with a YLAA? The manual says it can recover up to 85% of heat and up to 145°.

      I was wondering about using it as a heating/preheat for a makeup air unit.

      Thanks

      KSEA120 chiller Pic for attention. Not a YLAA but at same customer.”

      Member Post, Member Post and Member Post
      3 Comments
      • 45%….dang they are running that temp quite low. That’s a heavy mix and definitely yes there is a correction factor with glycol. Hopefully your pumps are sized correctly for use with glycol

        1
      • You can backup the target flow with correction factors for sure.
        If you select a standard unit Rated to ANSI standards with water, there will be a glycol correction factor for the evaporator heat exchanger. You can get close with the published data from Dowtherm. It will account for the pressure drop increase, and also the reduction in heat transfer at various temperature ranges. You will also need to verify with the evaporator manufacturer. (See screenshot i included).
        You should have this accounted for in the selection of the equipment. Most suppliers software have the ability to enter your desired specification into their system and size it accordingly.
        All of that said, Bill Wren is correct in saying to get the stamp of approval to eliminate any possibility of damaging a customer relationship.
        BTUs out = BTU’s in x 1.25 (approximately). The biggest change on a machine with a high concentration of glycol running in cooling mode is the evaporator / pump selection. You don’t want spend a bunch of extra money to get a machine thats oversized when it really just needed a different evaporator / pump selection. There are also other bells and whistles the OEM might require depending on what your design cooling temps are, and what your doing in cooling VS heating mode.
        Even if you do all of the math, and work with the rep 1 on 1 to get you the correct selection and data sheet. I would pay an engineer an hour before you order it to look it over and put their stamp on it.
        Its cheap insurance. Protect your reputation.
        Dow publishes their own literature as well you can look up. we have a guide we made on correction factors that we can send you if you want. Let me know

    Submit a Support Ticket

    Are you facing a technical problem with the website or the online portal?
    Submit a support ticket, and we will get back to you within 48 hours.

    ✓

    Ticket Submitted!

    Thank you! Your support ticket has been submitted. We will get back to you within 48 hours.

    The Chiller Guys Hub

    Join the Chiller Guys Community

    Create a free account to keep reading and unlock full access to our community.

    • Access the full news feed & discussions
    • Share knowledge with like minded guys
    • Get exclusive training content
    • Join thousands of chiller mechanics worldwide