Member Post posted an update
I have a York YK that is displaying thus fault. It supposed to be auto restart once the fault clears. It went down yesterday afternoon and I guess it never came back online. What should I be checking?
Member Post17 Comments-
hopefully someone can chime in, i haven’t ran into this.
Just an FYI, Only messages posted in private groups send out emails to all of the guys. you will get a faster response if you post it in a private group. see my screenshot -
-
that first one was probably not it check this the serial I believe is the comm between the ACC and the micro board as long as it is red it will not restart and means still exists
1-
-
-
@brian-medley thanks a lot. I believe I found the problem. Do you know what causes that?
-
@ronnie5 wow is that the ACCboard?
1
-
-
-
It’s the VSD Logic Board.
-
@ronnie5 the logic board is bad?
-
@the-chiller-guys that’s what it looks like. We’re getting one shipped over night so we should have it sometime today. We’ll see if that board is the main issue.
1
-
-
-
Do you guys know how to adjust the motor fla% for the new board? I see a little blue box on the VSD Logic Board that says fla% adjustment, but I don’t see any numbers on it. Also how can I tell if the fla% has been set on the optiview screen?
1 -
you have to set FLA to motor FLA, turn the Pot until you read true Motro FLa on the optiview motor screen
2 -
Something changed on those screens. They’re not the same as before.
-
-
@ronnie5 awesome man, looks like she’s running now?
1 -
JCI stands for JUST Change IT LOL
1 -
I was going to say your input power is showing an X which means its not getting feedback so look into the logic board. Looks like you’ve got her solved.
-